Limited Sprinkler & Standpipe Alterations

Limited Sprinkler Alterations

An alteration to a sprinkler system that is limited in scope that a licensed Fire Suppression Piping Contractor can do, falling into one of the following categories:

Category – 1

There is a $35,000 cost limitation in any 12 month period and only the following work can be done:

Category – 1
$35,000 cost limitation per building including appliance and labor in any 12 month period

  1. Changes that do not alter the type of sprinkler system

  2. New Sprinkler Heads: Install up to five new sprinkler heads off of an existing sprinkler system

  3. Rearrange Sprinkler Heads: Rearrange not more than 20 sprinkler heads in areas classified in light hazard occupancy, in restaurant service areas classified in Group 1 ordinary hazard occupancy, or in mercantile areas classified in Group 2 ordinary hazard occupancy

  4. Relocation of piping that does not affect the operation of the sprinkler system

  5. Replacement of parts required for the operation of a sprinkler system

Category – 2

No cost and time period limitation, but only the following work can be done:

Category – 2
Estimated cost of unlimited work, must include all appliance and labor costs

  1. Sprinkler Heads for Existing Sprinkler System: Replacement of sprinkler heads, provided that orifice sizes, type and deflector positions remain the same

Limited Standpipe Alterations

An alteration to an existing combined standpipe system that a licensed Fire Suppression Piping Contractor can do:

Category – 1
There is a $35,000 cost limitation in any 12 month period and only the following work can be done:

Category – 1
$35,000 cost limitation per building including appliance and labor in any 12 month period;
  1. Relocate Hose Source and Cabinets: Relocation of standpipe auxiliary hose sources and cabinets within 10 ft. of original location provided existing covered area is not affected

    Relocation must comply with the NYC Code requirements for a new installation

  2. Replace Parts: Replacement of parts required for operation of a combined standpipe system


Category – 2
No cost and time period limitation, but only the following work can be done:

Category – 2
Estimated cost of unlimited work, must include all appliance and labor costs

N/A


For use only with LAA Applications submitted on or after December 31, 2014.

Only one category and one work type can be filed per limited alteration application.