In completing standpipe work or equipment, Contractors should check the following applicable notes to ensure regulatory and Code compliance with NYC Building Code:
All standpipes and sprinkler risers must be painted red; this color-coding must be certified (BC 903.6). All buildings must comply. Branch piping does not require color-coded painting BB 2010-014.
*Note: Dedicated Standpipe Valve handles must be painted Red; combination SD/SP System Valve handles must be painted Yellow; all painting must be complete before the hydrostatic test.
COLOR CODING |
|||
|
Sprinkler |
Standpipe |
Combination |
Risers |
Red |
Red |
Red |
Branch Lines |
Not Required |
Not Required |
Not Required |
Handles |
Green |
Red |
Yellow |
FDC |
Green |
Red |
Yellow |
In gut rehabilitations and demolitions, a NYS licensed Professional Engineer or Registered Architect must obtain a variance from the NYC Fire Department’s Construction, Demolition & Abatement Unit to remove standpipes when the scope exceeds four (4) stories. Regardless of scope, FDNY notification is always required when any standpipes will be taken out of service.
Standpipe project work requires, per the Building Code, certain Special Inspection to be performed during, and at the end of construction based on scope of work, as per table below. The Registered Design Professional is responsible for indicating which Special Inspections are required at submission, and the Owner must engage a responsible Special Inspection Agency, per BC 1704.24.
Sprinkler Systems |
Per NYC Building Code (BC 1707.23), Standpipe systems Special Inspections are required to verify installation of materials, fitting hangers’ assemblies and signage, are per approved documents. In addition, Special Inspection must ensure that painting of system complies with BC 905.11 and BC 905.11.5. This portion of the inspection may be conducted periodically at incremental stages matching the progress of the work. Special inspector shall witness all required tests, both hydrostatic* and flow tests and ensure submission of Form FP 84 to FDNY |
Fire Resistant Penetrations and Joints |
Per BC 1707.27, Special Inspections for through-penetrations, membrane penetration fire stops, fire resistant joint systems, and perimeter fire barrier systems that are tested and listed in accordance with BC Sections 713.4.1.1.2, 713.4.1.2, 714.3 and 714.4 shall comply with Sections 1704.27.1 and 1704.27.2. |
Seismic Isolation Systems |
Per BC 1707.8, compliance of standpipe system piping to ensure earthquake protection of building and its occupants. |
Post-Installed Anchors |
Per BC 1704.32
|
*The Special Inspection Agency need not witness the hydrostatic pressure test when such test is witnessed by DOB Plumbing Inspector.*
*Contractors have the option to self-certify standpipe inspections.*
For standpipe work, Contractors have the option to either require a Department Inspection or submit a self-certification of the completed work. The Contractor must submit a notice of intent to self-certify, with the dates of these self-certified inspections to the Department, (online inspection request) and follow-up with the submission of results for self-certified inspections (online inspection results).
The Standpipe Enforcement Unit conducts a random audit of all self-certified notices to ensure compliance of inspected work with Code and regulations.
The Department’s online portal for scheduling appointments for required DOB inspections must be used. DOB NOW provides robust online accounts, making it easier to submit applications, make payments, schedule appointments, check the status of an application or inspection, pull permits, and make renewals.